Data CoolInstallation, Operation and Maintenance Manual2 and 3 tonAir, Water and Glycol Cooled DX and Chilled Water

Seite 2

102.2 Water/Glycol Cooled Unit PipingThe required field installed condenser water pipe sizes may or may not be the same as the connectionsizes at the

Seite 3 - Table of Contents

112.2.3 Connection Sizes, Water/Glycol Cooled UnitsEvaporator Water IN and OUTModel Connections, ODDACW/G 02 3/4”DACW/G 03 3/4”2.2.4 Connection Sizes

Seite 4

122.5 Humidifier PipingThe optional humidifier offered on Data Cool is a steam generator type with a disposable cylinder. Thehumidifier makeup water

Seite 5 - Model Identification

133.0 ELECTRICAL CONNECTIONSBefore proceeding with the electrical connections, make certain that the volts, hertzand phase correspond to that specifie

Seite 6 - 1.0 INSTALLATION

144.0 INSTALLATION OF REMOTE OUTDOOR HEAT EXCHANGER4.1 RiggingThis section covers outdoor condensing units and fluid coolers. Outdoor heat exchangers

Seite 7 - 1.6 Storage

154.3 Electrical ServiceRefer to Sections 3.1 to 3.5 for information regarding line voltage and control voltage wiring details.4.4 Air Cooled Condensi

Seite 8 - 2.0 PIPING

16Start the evaporator fan and compressor. Check the liquid line sight glass to get a feel for the approximatecharge. Bubbles in the sight glass are

Seite 9

175.3 Water/Glycol Cooled Split Systems5.3.1. Water/Glycol Cooled Split Systems ChargingAll water/glycol Data Cool units are split systems requiring f

Seite 10

185.4 Refrigerant HandlingThe use of recovery/recycling units is required by U.S. Environmental Protection Agency (EPA) regulations.Technicians who se

Seite 11 - 2.4 Condensate Drain Piping

196.2 Programmable Digital ThermostatA cooling only digital thermostat designed to provide accurate control, displays room temperature andcooling on m

Seite 12 - 2.7 Evacuation

2CONGRATULATIONS ON THE SELECTION OF A DATA AIRE PRECISION ENVIRONMENTALCONTROL SYSTEM. PROPER INSTALLATION, OPERATION AND MAINTENANCE OF THISEQUIPME

Seite 13 - 3.0 ELECTRICAL CONNECTIONS

20The wiring diagram in the evaporator will indicate field interface terminals to the secondary heat exchanger.The internal wiring of the heat exchang

Seite 14 - 4.1 Rigging

217.6 Refrigerant Filter DrierFactory installed refrigerant filter driers do not normally require maintenance. When replacingcompressors or other rep

Seite 15 - 5.0 CHARGING

228.0 Warranty PolicyData Aire Inc. warrants your Data Aire environmental control unit to be free from defects in material andworkmanship under normal

Seite 16

2310.0 Contact Data AireAddress:DATA AIRE INC.230 W. BLUERIDGE AVE.ORANGE, CA 92865Phone:714-921-6000800-347-AIRE (2473) Toll FreeFax:714-921-6010 Ma

Seite 17

24RECOMMENDED LINE SIZING FOR AIR COOLED SPLIT SYSTEMSUP TO 200 EQUIVALENT FEETLIQUID LINESSINGLE CIRCUIT SYSTEMSUnit Tons per EQUIVALENT FEETTonnage

Seite 18 - 6.0 CONTROLS

25Data Aire, Inc.Monthly Maintenance Inspection ChecklistModel No.__________________ Serial No. ____________________Prepared by: _______________ Date:

Seite 19 - 6.5 Wiring Diagrams

26Data Aire, Inc.Quarterly Maintenance Inspection ChecklistModel No. _______________________ Serial No. ___________________________Prepared by: ______

Seite 21 - 7.6 Refrigerant Filter Drier

28- F -Fan Speed Control Systems... 15Field PipingAir Cooled ... 9Chilled Water ...

Seite 22 - 8.0 Warranty Policy

29- L -Liquid Lines ...8, 9, 24Leak Testing ... 12LocatingEvaporator...

Seite 23 - 10.0 Contact Data Aire

3Table of ContentsMODEL IDENTIFICATION ...51.0 INSTALLATION...

Seite 24 - SUCTION LINES

Notes: _______________________________________________________________________________________________________________________________________________

Seite 26

230 W. BlueRidge AvenueOrange, CA 92865800-347-2473www.dataaire.com e-mail: [email protected] Member of the CS Group of Companies© 2011 Data A

Seite 27

4Table of Contents, continued5.0 CHARGING ...

Seite 28

5Model Identification

Seite 29

61.0 INSTALLATIONThere is no intent on the part of Data Aire, Inc. to define local codes or statutes which maysupercede common trade practices. The m

Seite 30

7Note to Installing Contractor: Condensation formation and frequent humidifier flushing (whenhumidifier is installed) are normal functions of this eq

Seite 31

82.0 PIPING2.1 Split Air Cooled Unit PipingRefer to the attached Line Sizing chart on page 24 for a guideline for sizing refrigerant lines. Theultima

Seite 32 - DACU-IOM-0807 Rev A

92.1.3Connection Sizes, Air Cooled UnitsModel Liquid SuctionDACU 02 1/2" 3/4" Note: Unit will have a Liquid Line andDACU 03 1/2" 3/4&q