Data CoolInstallation, Operation and Maintenance Manual2 and 3 tonAir, Water and Glycol Cooled DX and Chilled Water
102.2 Water/Glycol Cooled Unit PipingThe required field installed condenser water pipe sizes may or may not be the same as the connectionsizes at the
112.2.3 Connection Sizes, Water/Glycol Cooled UnitsEvaporator Water IN and OUTModel Connections, ODDACW/G 02 3/4”DACW/G 03 3/4”2.2.4 Connection Sizes
122.5 Humidifier PipingThe optional humidifier offered on Data Cool is a steam generator type with a disposable cylinder. Thehumidifier makeup water
133.0 ELECTRICAL CONNECTIONSBefore proceeding with the electrical connections, make certain that the volts, hertzand phase correspond to that specifie
144.0 INSTALLATION OF REMOTE OUTDOOR HEAT EXCHANGER4.1 RiggingThis section covers outdoor condensing units and fluid coolers. Outdoor heat exchangers
154.3 Electrical ServiceRefer to Sections 3.1 to 3.5 for information regarding line voltage and control voltage wiring details.4.4 Air Cooled Condensi
16Start the evaporator fan and compressor. Check the liquid line sight glass to get a feel for the approximatecharge. Bubbles in the sight glass are
175.3 Water/Glycol Cooled Split Systems5.3.1. Water/Glycol Cooled Split Systems ChargingAll water/glycol Data Cool units are split systems requiring f
185.4 Refrigerant HandlingThe use of recovery/recycling units is required by U.S. Environmental Protection Agency (EPA) regulations.Technicians who se
196.2 Programmable Digital ThermostatA cooling only digital thermostat designed to provide accurate control, displays room temperature andcooling on m
2CONGRATULATIONS ON THE SELECTION OF A DATA AIRE PRECISION ENVIRONMENTALCONTROL SYSTEM. PROPER INSTALLATION, OPERATION AND MAINTENANCE OF THISEQUIPME
20The wiring diagram in the evaporator will indicate field interface terminals to the secondary heat exchanger.The internal wiring of the heat exchang
217.6 Refrigerant Filter DrierFactory installed refrigerant filter driers do not normally require maintenance. When replacingcompressors or other rep
228.0 Warranty PolicyData Aire Inc. warrants your Data Aire environmental control unit to be free from defects in material andworkmanship under normal
2310.0 Contact Data AireAddress:DATA AIRE INC.230 W. BLUERIDGE AVE.ORANGE, CA 92865Phone:714-921-6000800-347-AIRE (2473) Toll FreeFax:714-921-6010 Ma
24RECOMMENDED LINE SIZING FOR AIR COOLED SPLIT SYSTEMSUP TO 200 EQUIVALENT FEETLIQUID LINESSINGLE CIRCUIT SYSTEMSUnit Tons per EQUIVALENT FEETTonnage
25Data Aire, Inc.Monthly Maintenance Inspection ChecklistModel No.__________________ Serial No. ____________________Prepared by: _______________ Date:
26Data Aire, Inc.Quarterly Maintenance Inspection ChecklistModel No. _______________________ Serial No. ___________________________Prepared by: ______
28- F -Fan Speed Control Systems... 15Field PipingAir Cooled ... 9Chilled Water ...
29- L -Liquid Lines ...8, 9, 24Leak Testing ... 12LocatingEvaporator...
3Table of ContentsMODEL IDENTIFICATION ...51.0 INSTALLATION...
Notes: _______________________________________________________________________________________________________________________________________________
230 W. BlueRidge AvenueOrange, CA 92865800-347-2473www.dataaire.com e-mail: [email protected] Member of the CS Group of Companies© 2011 Data A
4Table of Contents, continued5.0 CHARGING ...
5Model Identification
61.0 INSTALLATIONThere is no intent on the part of Data Aire, Inc. to define local codes or statutes which maysupercede common trade practices. The m
7Note to Installing Contractor: Condensation formation and frequent humidifier flushing (whenhumidifier is installed) are normal functions of this eq
82.0 PIPING2.1 Split Air Cooled Unit PipingRefer to the attached Line Sizing chart on page 24 for a guideline for sizing refrigerant lines. Theultima
92.1.3Connection Sizes, Air Cooled UnitsModel Liquid SuctionDACU 02 1/2" 3/4" Note: Unit will have a Liquid Line andDACU 03 1/2" 3/4&q