Options
1” Pre-Filter - Units may be ordered with a one inch pre- lter.
Pump Package - Centrifugal pump packages are available to
circulate water or water/glycol solution. Pumps are available
in various horsepower and voltage. Both 3400 and 1750 rpm
pumps are available as an option. Pumps ship loose or come
mounted in an optional pump enclosure. It is recommended on
units with dual pump applications that a 3-way water regulating
valve be used in lieu of the standard 2-way valve.
Pump Auto-Changeover - Dual pump packages may be provided
with a pump auto-changeover control and NEMA 4 ow switch
( eld installed). The pump auto-changeover control is factory
wired and mounted in the dry cooler control box. The pump au-
to-changeover control provides automatic pump changeover in
the event of a pump failure. Upon pump changeover, an audible
alarm will sound at the indoor unit and a message (“STANDBY
PUMP ON: CHECK PRIMARY PUMP”) will be displayed on
the unit microprocessor display.
Hot Gas Bypass - Hot gas bypass may be ordered for changing
load conditions. The hot gas bypass valve is installed between
the compressor discharge line and the leaving side of the expan-
sion valve through a side outlet distributor. The system with the
evaporator under full load will maintain pressure on the leaving
side of the hot gas bypass valve to keep the valve port closed.
Should the load on the evaporator decrease to the point where
the coil is below the desired setting, the pressure on the dis-
charge of the hot gas bypass will put pressure on the diaphragm
overcoming the spring pressure of the seat and allowing some
hot gas to mix with the normal liquid discharge of the expansion
valve raising the evaporator pressure. This reduces the cooling
capacity of the unit to match the load. The hot gas bypass valve
can be adjusted to “ ne tune” the unit to room conditions.
Pump Enclosures - Pump enclosures are available for either
single or dual pump applications*. Pump enclosures are vented
and weather resistant. When ordered with pumps, the pumps
are factory mounted in the enclosure ready for eld piping and
wiring. (* Due to the size of some pumps, a special oversized
enclosure can be made available.)
Integral Pump Enclosures - Pumps may be factory mounted as
an integral part of the dry cooler. A 30” extension is added to
the dry cooler. Pumps are pre-piped and wired. Shut-off valves
and ow switches are included. This con guration greatly re-
duces eld installation procedures.
Extended Compressor Warranty - Extended compressor war-
ranty is available from the manufacturer in addition to the stan-
dard warranty. The warranty is for replacement of compressors
and does not include labor. Contact you local representative for
period of coverage.
Remote Temperature and Humidity Sensors - Tempera-
ture and humidity sensors may be ordered for remote wall
mounting. Sensors are provided in a wall mount plastic case
for remote sensing of temperature and humidity. 25 feet of
shielded cable is provided for eld wiring.
Smoke Detector - A unit mounted smoke detector will
shut down the unit if smoke is sensed. The unit mounted
microprocessor will sound an alarm and display “SMOKE
DETECTOR: UNIT SHUTDOWN” message. The smoke
detector is mounted in the return air stream and is provided
with auxiliary contacts.
Unit Mounted Disconnect - A unit mounted non-automatic
disconnect switch is installed in the high voltage electrical
section. The operating mechanism prevents access to the
high voltage electrical components until switched to the
“OFF” position. The operating mechanism (handle) pro-
trudes through the decorative door.
Steam Generator Humidi er with Modulating Control -
Modulating control may be added to the steam generator
humidi er. Modulating control will allow the humidi er to
automatically adjust steam output to match changing room
conditions. Self-regulating auto ush is included.
3-Way Water Regulating Valve - A 3-way water regulating
valve for head pressure control may be ordered to replace
standard 2-way valve installed in unit. The 3-way valve
controls the water/glycol ow rate to meet the heat rejection
requirements under varying conditions. Recommended on
units with dual pump applications.
Condensate Pump - Condensate pumps may be ordered as
factory installed or for eld installation. Condensate pumps
are complete with sump, motor, and automatic control. The
pumps are rated for 130 GPH @ 20 ft maximum or 40 GPH
@ 20 feet with check valve. Pumps shipped loose are avail-
able in 115, 230, or 460 volt. If unit mounted and wired,
the pump will match the unit voltage. Not available in 575
volt.
Up ow Plenum - Up ow plenums are fully insulated and
have front discharge air grille. Side grilles for both or one
side are available. Plenums are 18 inches high and are
painted to match the unit color.
Floorstand - Floorstands are adjustable +/- 2 inches and
may be ordered with a factory installed turning vane or with
seismic construction.
60% Ef cient Filter - The standard 30% ef cient lter may
be replaced with 60% ef cient lter (based on ASHRAE
Std. 52.1-1992). Filters are 4 inch deep, pleated type.
(Note: Higher ef ciency lters are available - consult facto-
ry regarding ef ciency percentage and unit static pressures)