R-407C
MODEL NUMBER DTWD/U-08 DTWD/U-10 DTWD/U-13
CAPACITY in Btu/hr - gross
80° DB/67° WB 50% RH Total 113,600 144,100 176,300
Sensible 95,700 115,300 135,600
75° DB/62.5° WB 50% RH Total 105,500 134,100 163,500
Sensible 92,400 111,600 131,200
75° DB/61° WB 45% RH Total 102,000 130,400 158,600
Sensible 98,600 119,500 140,000
72° DB/60° WB 50% RH Total 100,700 128,100 155,800
Sensible 90,400 109,300 128,500
72° DB/58.6° WB 45% RH Total 97,500 124,800 151,500
Sensible 95,600 116,600 136,600
MODEL NUMBER DTGD/U-08 DTGD/U-10 DTGD/U-13
CAPACITY in Btu/hr - gross
80° DB/67° WB 50% RH Total 106,600 136,000 165,500
Sensible 93,200 112,200 131,500
75° DB/62.5° WB 50% RH Total 98,700 126,600 153,800
Sensible 89,700 108,500 127,200
75° DB/61° WB 45% RH Total 95,700 122,400 148,500
Sensible 94,500 116,100 135,700
72° DB/60° WB 50% RH Total 94,000 120,900 146,700
Sensible 87,600 106,200 124,600
72° DB/58.6° WB 45% RH Total 91,500 117,400 142,000
Sensible 90,800 113,300 132,400
BLOWER SECTION
Air ow - CFM 4,400 5,000 5,500
Standard Motor HP 3 5 5
External Static Pressure - inches of W.G. 0.5 0.5 0.5
Number of motors/fans 1/1 1/1 1/1
Maximum external static pressure Down ow 1.0 1.5 0.8
(Standard motor) Up ow 1.0 1.5 0.8
Maximum external static pressure Down ow 1.5 1.5 0.8
(Next size motor) Up ow 1.5 1.5 0.8
Next size motor - horsepower 5 7
1
/
2
7
1
/
2
GLYCOL COOLED: Performance data at OPTIONAL air ow
WATER COOLED: Performance data at OPTIONAL air ow