19 R-407C
WATER/GLYCOL COOLED: Performance data at STANDARD airfl ow
CONDENSER WATER (Maximum design water pressure 150 psi - High pressure valves optional)
Using 65° F EWT GPM 9.5 11.9 14.8
Pressure drop in PSI 4.1 4.1 3.5
Using 75° F EWT GPM 14.8 18.5 23.2
Pressure drop in PSI 4.5 4.5 4.1
Using 85° F EWT GPM 21 26.3 31.8
Pressure drop in PSI 7.1 7.1 4.5
Using Fluid Cooler GPM 28.0 35.0 43.0
Pressure drop in PSI 9.1 10.1 8.1
COMPRESSORS
Type Scroll Scroll Scroll
Quantity 1 1 1
Refrigerant R-407C R-407C R-407C
EVAPORATOR COIL
Face area - sq. ft. 12.2 12.2 12.2
Rows of coils 3 4 5
Face velocity in FPM 295 328 369
REHEAT SECTION
Electric Standard Standard Standard
kW 15 15 15
Capacity in Btu/hr 51,225 51,225 51,225
HUMIDIFIER SECTION
Steam generator Standard Standard Standard
kW 3.2 3.2 3.2
Capacity in lb/hr 10 10 10
FILTER SECTION (Pleated, 30% effi cient based on ASHRAE Std. 52.1-1992.)
Quantity/size 2 - 20x25x4 2 - 20x25x4 2 - 20x25x4
CONNECTION SIZES (Refer to Operation and Maintenance Manual for piping information between unit and dry cooler)
Condenser water - supply 1-5/8 1-5/8 1-5/8
Condenser water - return 1-5/8 1-5/8 1-5/8
Condensate drain 3/4 3/4 3/4
Humidifi er supply 1/4 1/4 1/4