Data Aire DAFC-11 Spezifikationen Seite 21

  • Herunterladen
  • Zu meinen Handbüchern hinzufügen
  • Drucken
  • Seite
    / 44
  • Inhaltsverzeichnis
  • LESEZEICHEN
  • Bewertet. / 5. Basierend auf Kundenbewertungen
Seitenansicht 20
21 R-407C
MODEL NUMBER DT*D/U-08 DT*D/U-10 DT*D/U-13
ELECTRICAL SECTION Next Size Motor
Electrical data based on: electric reheat - YES, steam generator humidi er - YES, and NEXT SIZE MOTOR.
208-230/3/60 FLA/MCA/MOP 80/97/110 94/113/125 106/129/150
460/3/60 FLA/MCA/MOP 38/46/50 43/52/60 48/58/70
575/3/60 FLA/MCA/MOP 29/36/40 33/40/45 40/48/60
Electrical data based on: electric reheat - NO, steam generator humidi er - YES, and NEXT SIZE MOTOR.
208-230/3/60 FLA/MCA/MOP 54/65/90 68/82/110 80/97/125
460/3/60 FLA/MCA/MOP 27/32/45 31/37/50 36/44/60
575/3/60 FLA/MCA/MOP 20/24/30 24/28/35 30/37/50
Electric data based on: electric rehear - YES, steam generator humidi er - NO, and NEXT SIZE MOTOR.
208-230/3/60 FLA/MCA/MOP 80/97/110 94/113/125 106/129/150
460/3/60 FLA/MCA/MOP 38/46/50 43/52/60 48/58/70
575/3/60 FLA/MCA/MOP 29/36/40 33/40/45 40/48/60
Electrical data based on: electric reheat - NO, steam generator humidi er -NO, and NEXT SIZE MOTOR.
230/3/60 FLA/MCA/MOP 38/45/70 52/61/90 64/76/125
460/3/60 FLA/MCA/MOP 19/23/35 24/28/45 29/35/50
575/3/60 FLA/MCA/MOP 14/17/25 18/21/30 25/29/45
 NEXT SIZE MOTOR
Motor horsepower 3 5 5
203-230/3/60 FLA 9.0 14.6 14.6
460/3/60 FLA 4.4 6.6 6.6
575/3/60 FLA 3.3 5.3 5.3
OUTDOOR DRY COOLER
Dry cooler selection at 95° F ambient DAFC-15 DAFC-21 DAFC-21
Dry cooler selection at 100° F ambient DAFC-21 DAFC-24 DAFC-30
(Note: Dry coolers are selected at sea level. Refer to page 32 for dry cooler electrical data)
* - W for water or G for glycol
FLA - Full load amps
MCA - Minimum circuit amps (wire sizing amps)
MOP - Maximum overcurrent protection device amps
WATER/GLYCOL COOLED: Performance data at STANDARD air ow