18
R-407C
MODEL NUMBER DTWD/U-08 DTWD/U-10 DTWD/U-13
CAPACITY in Btu/hr - gross
80° DB/67° WB 50% RH Total 109,900 139,400 170,200
Sensible 85,500 102,100 121,600
75° DB/62.5° WB 50% RH Total 102,000 129,600 158,100
Sensible 82,700 99,100 118,100
75° DB/61° WB 45% RH Total 99,300 126,600 153,800
Sensible 88,500 105,800 125,600
72° DB/60° WB 50% RH Total 97,200 123,600 150,700
Sensible 81,000 97,300 116,000
72° DB/58.6° WB 45% RH Total 94,900 121,100 146,900
Sensible 86,400 103,500 122,800
MODEL NUMBER DTGD/U-08 DTGD/U-10 DTGD/U-13
CAPACITY in Btu/hr - gross
80° DB/67° WB 50% RH Total 103,100 131,300 159,600
Sensible 82,900 99,000 117,400
75° DB/62.5° WB 50% RH Total 95,600 122,000 148,400
Sensible 80,100 95,900 113,900
75° DB/61° WB 45% RH Total 92,800 119,100 144,300
Sensible 85,800 102,600 121,400
72° DB/60° WB 50% RH Total 91,100 116,400 141,700
Sensible 78,400 94,100 111,800
72° DB/58.6° WB 45% RH Total 88,600 114,000 138,000
Sensible 83,600 100,200 118,600
BLOWER SECTION
Airfl ow in CFM 3,600 4,000 4,500
Standard motor HP 2 3 3
External Static Pressure - inches of W.G. 0.5 0.5 0.5
Number of motors/fans 1/1 1/1 1/1
Maximum external static pressure Downfl ow 0.8 1.5 0.6
(Standard motor) Upfl ow 0.8 1.5 0.6
Maximum external static pressure Downfl ow 1.5 1.5 1.5
(Next size motor) Upfl ow 1.5 1.5 1.5
Next size motor - horsepower 3 5 5
WATER COOLED: Performance at STANDARD airfl ow
GLYCOL COOLED: Performance at STANDARD airfl ow